TECHNICAL SPECIFICATIONS
1. Mixing chamber
New air with simulation resistances of inlet temperature 2 x 6 kW
Recycled air
Command by servo engine with opening indicator
Protection elements
2. Filtration
Rough gravimetric filter
Opacimetric fine filter
3. Refrigeration
R 134 a fluid
Evaporator settled in the chamber - power 13.5 kW
Condensor outside
Compressor, liquid tank, dehydrator, shock proof liquid bottle
Recuperation tank of condensates
4. Adiabatic washer
3 pulverisation buses
Adjustable pressure and flow maxi 40 L/min - 3.3 bars
Transparent buffer tank and recuperation tank
5. Dried vapour humidifier
Capacity : 6 kg/h
Regulation and controller with digital display
Recuperation tank
6. Electric battery
Antifreeze function
Preheating function
Heating 2 x 6 kW function |
7. Fan
Nominal flow : 2000 m3/h
Nominal speed : 1400 tr./min
Speed variator
Programmable flow and flow variations
Outlet valve.
8. Instrumentation
Five temperature measurements
Five relative humidity measurements
An eight column manometer in order to measure 8
∆P on the
veine
A Pitot Tube
Portable thermometer and contact probe
Refrigeration fluid flowmeter
High pressure manometer
Low pressure manometer
High pressure controller
Low pressure controller
Combined pressure controller
Pump down regulation thermostat
9. Separable chassis in two parts independently transportable
Dismountable and transparent lateral pans
Cross section
10. Additional equipment
Iced water battery
Flowmeter to adiabatic washer pump discharge |